Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 04/02/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CALLED ELEC. CONTR. THAT INSP. WOULD TAKE PLACE MONDAY. |
| 03/31/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0236*/ CORRECTIONS REQUIRED: 1) COMPLETE CIRCUIT INDEX. 2) REPLACE CHASE NIPPLE WITH SHORT NIPPLE AND LOCK-NUTS. CHASE NIPPLES ARE NOT PERMITTED TO TERMINATE CONDUIT FITTINGS TO BOXES (MAIN PNL) 3) WHERE IS 2ND GROUND ROD AND BONDING OF GAS AND WTR PIPING. LEAVE INSTRUCTIONS IN PANEL. |