Permit: T04EL00568

Parcel: 12218226B

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/05/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
04/02/2004 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*/ CALLED ELEC. CONTR. THAT INSP. WOULD TAKE PLACE MONDAY.
03/31/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0236*/ CORRECTIONS REQUIRED: 1) COMPLETE CIRCUIT INDEX. 2) REPLACE CHASE NIPPLE WITH SHORT NIPPLE AND LOCK-NUTS. CHASE NIPPLES ARE NOT PERMITTED TO TERMINATE CONDUIT FITTINGS TO BOXES (MAIN PNL) 3) WHERE IS 2ND GROUND ROD AND BONDING OF GAS AND WTR PIPING. LEAVE INSTRUCTIONS IN PANEL.