Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*1) OK TO CLEAR |
| 03/26/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) USE ACORN GROUND CLAMPS AS PER MANUFACTURER INSTRUCTIONS. ONE CONDUCTOR ONLY 2) GAS BOND TO BE ON INTERIOR PIPING 3) BOND JUNCTION BOX 4) TIGHTEN LOOSE FITTINGS 5) ENTRANCES ABOVE CURRENT CARRING PARTS TO HAVE AN APPROVED SEALING DEVICE 6) STRAP GROUND TO BUILDING 7) RISER HARDWARE TO BE 1/4" MINIMUM 8) MAINTAIN 3' FROM GAS REGULATOR |