Permit: T04EL00564

Parcel: 111060270

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/24/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ 1) THE 200 AMP SERVICE REQUIRES TWO 5/8" X 8' GROUND RODS. 2) LAND THE UFER WIRE ON THE NUETRAL BAR - NOT THE CAN. THE CAN IS ALREADY BONDED TO THE NUETRAL BAR. SEE ART 250 - " GROUNDING THE SERVICE GROUNDED CONDUCTOR"