Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/08/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL GFCI RECEPTACLE FOR WASHER, OUTLET IS NOT SUPPORTED AND NOT GFCI 2) MUST ALSO BE IN W/P BOX AND HAVE BUBBLE TYPE COVER |
|
| 10/13/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANNOT USE OLD PANEL BOX FOR JUNCTION- CALL BACK ONCE POWER CHANGED OVER. CANNOT USE OLD PANEL BOX FOR JUNCTION. |
|
| 06/18/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) TWO GROUND RODS REQUIRED 6' APART. 2) INSTALL PERM. ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO ENCLOSURE. 3) INSTALL ΒΌ" MIN. BOLT TO SUPPORT RISER CONDUIT. |