Permit: T04EL00547

Parcel: 116160610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) GROUNDING REQUIRES TWO GROUND RODS SET 6' APART AND CONNECT IN PARRALEL WITH #4 COPPER WIRE RUN TO NUETRAL BARS OF MAIN PANEL. 2) THE GAS PIPING MUST BE GROUNDED AT POINT OF ENTRANCE TO HOUSE. 3) TEP REQUIRES A MIN. 2" RIDGID PIPE/CONDUIT RISER FOR SERVICE CONDUCTORS. 4) TWO STRAPS ARE REQUIRED TO SUPPORT RISER PIPE TO STRUCTURE. ΒΌ" LAG BOLT SIZE IS MIN. 5) CIRCUIT CONDUCTORS MAY BE UNDERSIZED FOR BREAKER AVERAGES.