Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/23/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) GROUNDING REQUIRES TWO GROUND RODS SET 6' APART AND CONNECT IN PARRALEL WITH #4 COPPER WIRE RUN TO NUETRAL BARS OF MAIN PANEL. 2) THE GAS PIPING MUST BE GROUNDED AT POINT OF ENTRANCE TO HOUSE. 3) TEP REQUIRES A MIN. 2" RIDGID PIPE/CONDUIT RISER FOR SERVICE CONDUCTORS. 4) TWO STRAPS ARE REQUIRED TO SUPPORT RISER PIPE TO STRUCTURE. ΒΌ" LAG BOLT SIZE IS MIN. 5) CIRCUIT CONDUCTORS MAY BE UNDERSIZED FOR BREAKER AVERAGES. |