Permit: T04EL00537

Parcel: 122183660


Addresses:

3531 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/22/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
03/18/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*/ 1) ADD TWO STRAPS TO RISER PIPE. ONE MUST BE WITHIN 8" OF THE TOP OF THE PANEL 2) RUN A GROUND TO THE GAS LINE. ATTACH TO HOUSE SIDE PIPING. SEE NEC. ART. 250.54 94' 3) PUT GROUND WIRES IN POCKET SIDE OF ROD GROUND CLAMP (OPPOSITE OF BOLT SIDE)