Permit: T04EL00533

Parcel: 110080720


Addresses:

2601 N ORCHARD AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/26/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
03/22/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) ADDRESS LABEL TO BE ABLE TO WITHSTAND THE ELEMENTS, SHOULD BE METAL 2) SUPPORT GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 3) USE AN APPROVED FITTING WITH L.B.-CHASE NIPPLE NOT APPROVED 4) AN APPROVED SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 5) SUPPORT CONDUIT BELOW PANEL AND ABOVE 6) TIGHTEN LOOSE FITTINGS 7) RISER SUPPORTS TO BE 1/4" MINIMUM 8) BOND JUNCTION BOX 9) ONLY ON CONDUTOR PER LUG 10) BOND JUMPER TO BE SIZED PER 250.122