Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/25/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) YOUR METER HIEGHT EXCEEDS TEP REQUIREMENT. HAVE TEP INSPECT AND DECIDE IF METER LOCATION IS ACCEPTABLE TO THEM. 2) A STRAP IS REQUIRED ON THE RISER PIPE AT +/- 8" ABOVE PANEL. 3) THR GROUND/NEUTRAL TO SUB-PANEL MUST TERMINATE ON EITHER SIDE NEUTRAL/GROUND BUS IN PANEL, NOT ON METAL OF CAN. 4) THE OLD SUB-PANEL NEUTRAL/GROUND CONNECTION MUST BE REMOVED. 5) TY-RAPS ARE NOT AN APPROVED METHOD OF SUPPORT FOR ELECTRICAL CONDUIT OR WIRE. STRAP GROUND WIRE TO BRICK. |