Permit: T04EL00490

Parcel: 127034040


Addresses:

5731 E 3RD ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00490

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR
04/07/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CONTRACTORS SCOPE OF WORK IS COMPLETE FINAL IS SUBJECT TO OWNER 2) OBTAINING A NEW PERMIT FOR NEW CIRCUITS INSTALLED
04/01/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CIRCUITS ARE NEW INSTALLATIONS NOT EXISTING OR HAVE BEEN INSTALLED WITHOUT A PERMIT. FINISH #5 OF PREVIOUS INSPECTION
03/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) A GAS BOND IS NEEDED. 2) BOND JUNCTION BOXES - COVER DOES NOT FIT BACK ON. 3) USE AN APPROVED FITTING AT L.B. - CHASE NIPPLE NOT APPROVED OR CUT UP ALTERED FITTING. 4) USE CORRECT SIZE CONDUCTOR FOR BREAKER AMPACITY. 5) ADD NEW DRYER CIRCUIT TO PERMIT AND NEW 20 AMP CIRCUIT. 6) WHITE THHN NOT ALLOWED TO BE UNGROUNDED CONDUCTOR IN RACEWAY. 7) GROUNDING EQUIPMENT CONDUCTOR NOT TO BE DOWNSIZED AT SPLICE.