Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00490
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK TO CLEAR | |
04/07/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) CONTRACTORS SCOPE OF WORK IS COMPLETE FINAL IS SUBJECT TO OWNER 2) OBTAINING A NEW PERMIT FOR NEW CIRCUITS INSTALLED | |
04/01/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) CIRCUITS ARE NEW INSTALLATIONS NOT EXISTING OR HAVE BEEN INSTALLED WITHOUT A PERMIT. FINISH #5 OF PREVIOUS INSPECTION | |
03/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) A GAS BOND IS NEEDED. 2) BOND JUNCTION BOXES - COVER DOES NOT FIT BACK ON. 3) USE AN APPROVED FITTING AT L.B. - CHASE NIPPLE NOT APPROVED OR CUT UP ALTERED FITTING. 4) USE CORRECT SIZE CONDUCTOR FOR BREAKER AMPACITY. 5) ADD NEW DRYER CIRCUIT TO PERMIT AND NEW 20 AMP CIRCUIT. 6) WHITE THHN NOT ALLOWED TO BE UNGROUNDED CONDUCTOR IN RACEWAY. 7) GROUNDING EQUIPMENT CONDUCTOR NOT TO BE DOWNSIZED AT SPLICE. |