Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/15/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/12/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ FINISH ITEMS 3&4 AS DISCUSSED - A LABEL FOR DISCONNECTING, CLOSE UP ALL SEALS FOR 5 THREAD CONTACT. |
| 03/11/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MIX CHICO AS PER MANUFACTURERS INSTRUCTIONS. WE HAVE A POWDER CONSISTENCY NOW NOT HARD OR LIQUID. 2) JUNCTION BOXES TO BE GROUNDED, 250-148, 504-50, 250-100, BOTH INTRISTCLY SAFE AND 110 POWER, 514-16. 3) PLEASE COMPLY WITH 514-6. 4) MAKE SURE OF 5 THREAD CONTACT ON THREADED CONNECTORS. |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |