Permit: T04EL00388

Parcel: 120071840


Addresses:

4113 S BELMAR AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/13/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) NO COMPLIANCE WITH NOTE # 1, 4, 6. 2) NEED TO VERIFY WATER AND GAS BONDING. 3) UNCOVER GROUND WIRE AND GROUND ROD CONNECTIONS. - MARKING PEN NOT ALLOWED FOR ADDRESS. USE ΒΌ" BOLTS TO SUPPORT RISER CONDUIT. - SERVICE IS 100 AMP, NOT 200 AMP, CHANGE DESCRIPTION ON PERMIT. SEE NOTES LAST INSP.
02/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. MUST BE SCREWED OR RIVITED 2) 2 GROUND RODS REQUIRED, 6' MINIMUM APART 3) MUST BOND WATER AND GAS PIPING 4) SUPPORT RISER WITHIN 3' OF SERVICE ENCLOSURE. USE MINIMUM 1/4" BOLTS 5) SUPPORT 1/2" AND 3/4" CONDUIT 6) CHANGE SERVICE DESCRIPTION TO 100 AMP UPGRADE, NOT 200 AMP, 100 AMP INSTALLED