Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00370
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2004 | ELECTRIC - FINAL | Approved | ||
| 03/23/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ A RE-INSPECTION FEE IS DUE PRIOR TO NEXT INSP. / 300-5 REQUIRE PVC CONDUIT (AS APPLIED) TO BE A MIN. OF 18" DEEP. TOP ENTRY INTO METER SECTION NOT APPROVED. NOT ACCESSABLE AND MUST KEEP UTILITY CONDUCTOR SUPPORTED IN ITS OWN DEDICATED SECTION 230.7 | |
| 03/17/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 2" CONDUIT MUST BE 18" BELOW GRADE. TOP ENTRY INTO THIS METER COMBO SERVICE IS RENDERED NOT ACCESSABLE AND IS COMBINING CUSTOMER WIRING WITH UTILITY WIRING. PLEASE VERIFY THAT ALL BRANCH CIRCUIT RATINGS ARE 20 AMPS OR MORE. WTR LINE IN FRONT OF SERVICE VIOLATES 110-26 NEC. |