Permit: T04EL00364

Parcel: 11304174A


Addresses:

926 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00364

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/24/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ 1) INSTALLATION OF NEW SERVICES REQUIRES TWO 5/8" X 8' GROUND RODS BE INSTALLED. THE RODS MUST BE SEPERATED BY A MIN. DISTANCE OF 6'. 2) THE 1" AND 3/4" EMT PIPES ENTERING TOP OF PANEL ARE IMPROPERLY TERMINATED. BOTH ARE GAPPED AND THE PANEL IS SUBJECT TO WATER LEAK. THE 1" IS IMPROPERLY TERMINATED AT JUNCTION BOX. CORRECT AND RECALL.
02/26/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ 1) COMPLETE THE CIRCUIT DIRECTORY 2) INSTALL PERMANENT METAL (EMBOSSED) ADDRESS NUMBERS ABOVE OR BELOW METER. ATTACH WITH RIVETS OR SCREWS. PEN, PENCIL, "MAGIC MARKER", "CRAYON" ETC. ARE NOT ACCEPTABLE 3) INSTALL A SEPERATE CIRCUIT BREAKER FOR THE LIGHTING ARRESTOR. REMOVE FROM SERVICE CONDUCTOR SIDE OF MAIN C/B. REFER TO MANUFACTURERS INSTRUCTIONS 4) EXPOSE GROUND ROD ENDS DOWN TO CLAMP FOR INSPECTION 5) WHERE ARE COLD WATER AND GAS PIPING BONDED ? LEAVE WRITTEN INFO. RECALL WHEN COMPLETED