Permit: T04EL00355

Parcel: 12302029A


Addresses:

2225 N MARGARET AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 03/11/04AM
03/08/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ BE ADVISED: THE FOLLOWING MUST BE DONE. 1) THE DDRESS ON THE MAIN PANEL MUST BE A METAL STRIP SCREWED OR RIVITED TO BOX. PENCIL, PEN, MAGIC MARKER, CRAYON ETC, ARE NOT DURABLE AND THEREFORE ARE UNACCEPTABLE. NUMBERS MAY ALSO BE STAMPED OR ENGRAVED ON METAL. 2) THE GROUNDING SYSTEM CONDUCTOR MUST BE RUN UNSPLICED TO THE GROUNDING RODS FROM THE PANEL. THE WTR PIPE AND THE GAS PIPE GROUND MAY BE SPLICED TO THE MAIN GROUND CONDUCTOR.
03/01/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*