Permit: T04EL00355

Parcel: 12302029A


Addresses:

2225 N MARGARET AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection 0000*
03/01/2004 ELECTRIC - SERVICE RELOCATION Not ready for Inspection IVRS - Inspection 0000*/ 1) ONLY ONE CONDUCTOR UNDER OPENING IN GROUND CLAMP ALLOWED 2) A GAS AND WATER BOND ARE NEEDED 3) IDENTIFY NEUTRAL CONDUCTOR CORRECTLY AT BOTH ENDS. ALSO ROUTE SAFELY THROUGH METER ? 4) LABEL BREAKERS 5) NEED TO SEE JUNCTION BOX WITH NEW WIRING 6) FILL UNUSED OPENING IN BOTTOM OF PANEL 7) WHAT IS THE CONNECTION POINT FOR OLD SERVICE AFTER UPGRADE ?