Permit: T04EL00343

Parcel: 12302003A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
03/03/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000* SENT TO TEP ON 03/04/04AM
03/02/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0210*/ 1) THE GAS AND WATER PIPES MUST BE BONDED TO THE SERVICE PANEL. 2) THE UFER GROUND MUST BE LANDED AND TERMINATED IN THE MAIN PANEL INSTEAD OF THE METER CAN. THE GROUND MUST BE READILY INSPECTABLE, SO IT CANNOT BE LOCATED IN A T.E.P. SEALED SECTION. 3) STRAP THE GROUND WIRE SECURELY TO THE WALL. 4) REMOVE THE OLD GROUND WIRE. 5) SINK ROD ENDS 2" BELOW GRADE. RECALL WHEN READY.