Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/2004 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 02/19/2004 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0235*/ 1) THE GROUND RODS MUST BE CONNECTED IN LINE, ROD TO ROD TO PANEL, TO ACHIEVE THE DESIRED 25 OHM [OR LESS] RESISTANCE. 2) WHERE ARE WATER LINE AND GAS LINES GROUNDED. 3) THE ADDRESS ON THE PANEL MUST BE THE SAME AS ON THIS PERMIT. 4) ADD A PIPE STRAP TO RISER PIPE WITHIN 8" OF PANEL BOX. |