Permit: T04EL00301

Parcel: 140250860

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR RECONNECTT #21 2) SENT TO TEP ON 02/24/04AM
02/17/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) OLD ROMEX UNDER OVERHANG [ROOF] NEEDS TO BE REPLACED, EXISTING IS DAMAGED. 2) TRIPLE LUGGING IN SERVICE DISCONNECT NOT ALLOWED. ALSO SMALL SUB-PANEL OVERFUSED. IF NOT ABANDONED, INSTALL FUSE TAMPER INSERTS FOR 20 AMP FUSES. 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. 4) INSTALL SMOKE DETECTORS EACH BEDROOM. 5) RE-CONNECT #4 BARE GROUND. WHY WAS IT CUT OFF? WORK MUST BE DONE BY C-11 LICENSED CONTR.