Permit: T04EL00294

Parcel: 135082840

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/23/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/11/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ ALL FORIEGN SYSTEMS TO THE ELEC. SUBJVENT TO THE METER/COMBO PANELBOARD MUST BE REMOVED. SEE N.E.C. 99, 110-26 AND COMPLY.
02/23/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) RODS MUST BE 6' APART MIN. 2) SERVICE UPGRADED OVER EXISTING WATER LINES. IMPROPER CLEARANCES - NEC 110.26. 3) NEED GAS BOND. 4) USE ONLY BREAKERS LISTED FOR THIS PANEL BOARD. 5) NEED PERMANENT METAL ADDRESS TAG, WITH SCREWS.
02/19/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*/ LOCKED - PLEASE RECALL INSPECTION.