Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR INCREASE 2) SENT TO TEP ON 02/27/04 |
| 02/24/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) ADDRESS TAG MUST BE SCREWED OR RIVITED TO ENCLOSURE 2) USE MINIMUM 1/4" BOLTS TO SUPPORT RISER 3) SUPPORT PVC AT 3' INTERVALS PER NEC. PVC EXPOSED MUST BE SCHEDULE 80 PER CITY OF TUCSON ORDINANCE 4) ADD NEW DRYER CIRCUIT TO PERMIT |