Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/08/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE TERMINATE ALL STRANDS OF CONDUCTOR UNDER LUG. 2) UNGROUNDED CONDUCTOR TO BE CORRECTLY IDENTIFIED. 3) BREAKER TO BE LISTED FOR USE BY MANUFACTURER. 4) PLEASE VERIFY PERMIT FOR NEW A/C |
| 03/25/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WORK PROGRESS |
| 02/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ CORDS CANNOT BE USED FOR PERMANENT WIRING MEANS. SE CABLE PROTECTION TO BE NON-FLEXIBLE RACEWAY ALSO OTHER CABLES AND CONDUCTORS. 373-5 [C] |