Permit: T04EL00266

Parcel: 12213140A


Addresses:

1307 N COLUMBUS BL


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T04EL00266

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR. WILL NOTIFY TEP
02/12/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*/ 1) THE 4-11/16 JUNCTION BOX BY WTR HTR NOT WEATHER PROOF. 2) THE SE CABLE FEEDING THE JUNCTION BOX NEEDS TO BE PHYSICALLY PROTECTED. 3) THE GROUNDING TO DISCONNECT IS IMPROPER, GROUND WIR CUT OFF BEHIND WTR HTR. 4) BEDROOMS REQUIRE SMOKE DETECTORS. 5) RECEPTACLE BY KITCHEN SINK TO BE GFI PROTECTECTED. 6) FUSE BOX INSIDE AT STORAGE ROOM OR CLOSET HAS A DOUBLE LUG SITUATION WHICH MUST BE CORRECTED. BOX IS LOOSE, FUSE BOX INSTALLED INCORRECTLY, ALL HOLES TO HAVE BUSHINGS, CANNOT PUT FUSE BOX OVER A JUNCTION BOX AND CONCEAL IT. 7) CANNOT LOCATE SERVICE FOR THIS UNIT - NEED TO INSPECT IT. OBTAIN THE SERVICES OF A LICENCED ELECTRICAL CONTRACTOR TO MAKE REPAIRS.