Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T04EL00266
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000*/ 1) OK TO CLEAR. WILL NOTIFY TEP | |
02/12/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*/ 1) THE 4-11/16 JUNCTION BOX BY WTR HTR NOT WEATHER PROOF. 2) THE SE CABLE FEEDING THE JUNCTION BOX NEEDS TO BE PHYSICALLY PROTECTED. 3) THE GROUNDING TO DISCONNECT IS IMPROPER, GROUND WIR CUT OFF BEHIND WTR HTR. 4) BEDROOMS REQUIRE SMOKE DETECTORS. 5) RECEPTACLE BY KITCHEN SINK TO BE GFI PROTECTECTED. 6) FUSE BOX INSIDE AT STORAGE ROOM OR CLOSET HAS A DOUBLE LUG SITUATION WHICH MUST BE CORRECTED. BOX IS LOOSE, FUSE BOX INSTALLED INCORRECTLY, ALL HOLES TO HAVE BUSHINGS, CANNOT PUT FUSE BOX OVER A JUNCTION BOX AND CONCEAL IT. 7) CANNOT LOCATE SERVICE FOR THIS UNIT - NEED TO INSPECT IT. OBTAIN THE SERVICES OF A LICENCED ELECTRICAL CONTRACTOR TO MAKE REPAIRS. |