Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 02/13/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) A GROUNDING ELECTRODE SYSTEM IS NEEDED - 2 GROUND RODS. 2) A GAS AND WATER BOND AS PER 250-104. 3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR. 4) BOND JUNCTION BOX. 5) RISER STRAP TO BE ΒΌ" MIN. HARDWARE. 6) NO MORE THAN 360o IN A CONDUIT RUN. 7) PLEASE ADD NEW CIRCUITS TO PERMIT AND PROVIDE ACCESS FOR INSPECTION. 8) FINISH CONNECTION OF CIRCUITS. 9) A PERMANENT METAL ADDRESS IS NEEDED. |