Permit: T04EL00262

Parcel: 130070140


Addresses:

3726 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/17/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
02/13/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) A GROUNDING ELECTRODE SYSTEM IS NEEDED - 2 GROUND RODS. 2) A GAS AND WATER BOND AS PER 250-104. 3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR. 4) BOND JUNCTION BOX. 5) RISER STRAP TO BE ΒΌ" MIN. HARDWARE. 6) NO MORE THAN 360o IN A CONDUIT RUN. 7) PLEASE ADD NEW CIRCUITS TO PERMIT AND PROVIDE ACCESS FOR INSPECTION. 8) FINISH CONNECTION OF CIRCUITS. 9) A PERMANENT METAL ADDRESS IS NEEDED.