Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 03/05/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* DO NOT MIX COPPER AND ALUMINUM IN WIRE NUT. LOAD CONDUCTOR NOT TO EXIT THROUGH TOP END WALL. SEE LISTING. CANNOT HAVE PRE ? WIRING GOING THROUGH UTILITY DEDICATED, UNPROTECTED AREA ( UPPER PROTION OF SERVICE) . A GROUNDING ELECTRODE SYSTEM IS REQUIRED ALONG WITH WATER AND GAS BOND |