Permit: T04EL00261

Parcel: 126131110


Addresses:

4655 E 14TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/09/2004 ELECTRIC - SERVICE UPGRADE Approved
03/05/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* DO NOT MIX COPPER AND ALUMINUM IN WIRE NUT. LOAD CONDUCTOR NOT TO EXIT THROUGH TOP END WALL. SEE LISTING. CANNOT HAVE PRE ? WIRING GOING THROUGH UTILITY DEDICATED, UNPROTECTED AREA ( UPPER PROTION OF SERVICE) . A GROUNDING ELECTRODE SYSTEM IS REQUIRED ALONG WITH WATER AND GAS BOND