Permit: T04EL00260

Parcel: 131112830

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00260

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/19/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
02/13/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ DRIVE RODS FLUSH BELOW GRADE. INSTALL ROOF JACK. BOND BOTH ENDS OF CONDUIT ENCLOSING GROUND WIRE.