Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00238
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* SENT TO TEP ON 02/27/04AM | |
02/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) IDENTIFY BRANCH CIRCUIT 110.22. 2) #10 CU. AWG FOR MAIN GROUNDING ELECTRODE CONDUCTOR IS SIZED BELOW THE MIN. OF #8 CU. AWG - 250.66 - SIZE TO #4 - 250.64[B]. 3) RE-IDENTIFY NUETRAL SERVICE ENTRANCE CONDUCTOR FROM GREEN TO WHITE 200.6, ALSO I.D. AT WEATHERHEAD. 4) NOTE: THE NUMBER 8[?] SERVICE ENTRANCE NUETRAL IS SIZED OK IF THE UNDERGROUNDED SERVICE ENTRANCE CONDUCTOR IS #2 AWG CU. 5) NOTE: INTERIOR CIRCUITS RATED 20 AMPS? 6) USE ALL ΒΌ" HARDWARE FOR RISER SUPPORTS. 7) ACORN CLAMP SUITABLE FOR ONE TERMINATION. 8) EXPOSE 2ND GROUND ROD. 9) NEED WTR AND GAS BOND. A COMMON GROUNDING ELECTRODE SYSTEM IS REQUIRED FOR ALL OF THE SERVICES INSTALLED. |