Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04EL00238

Parcel: 117143140


Addresses:

517 S MAIN AV #C


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00238

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 02/27/04AM
02/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) IDENTIFY BRANCH CIRCUIT 110.22. 2) #10 CU. AWG FOR MAIN GROUNDING ELECTRODE CONDUCTOR IS SIZED BELOW THE MIN. OF #8 CU. AWG - 250.66 - SIZE TO #4 - 250.64[B]. 3) RE-IDENTIFY NUETRAL SERVICE ENTRANCE CONDUCTOR FROM GREEN TO WHITE 200.6, ALSO I.D. AT WEATHERHEAD. 4) NOTE: THE NUMBER 8[?] SERVICE ENTRANCE NUETRAL IS SIZED OK IF THE UNDERGROUNDED SERVICE ENTRANCE CONDUCTOR IS #2 AWG CU. 5) NOTE: INTERIOR CIRCUITS RATED 20 AMPS? 6) USE ALL ΒΌ" HARDWARE FOR RISER SUPPORTS. 7) ACORN CLAMP SUITABLE FOR ONE TERMINATION. 8) EXPOSE 2ND GROUND ROD. 9) NEED WTR AND GAS BOND. A COMMON GROUNDING ELECTRODE SYSTEM IS REQUIRED FOR ALL OF THE SERVICES INSTALLED.