Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00237
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* SENT TO TEP 03/05/04 915AM | |
02/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) IDENTIFY BRANCH CIRCUIT 110.22. 2) #10 CU. AWG FOR MAIN GROUNDING ELECTRODE CONDUCTOR IS SIZED BELOW THE MIN. OF #8 CU. AWG - 250.66 - SIZE TO #4 - 250.64[B]. 3) RE-IDENTIFY NUETRAL SERVICE ENTRANCE CONDUCTOR FROM GREEN TO WHITE 200.6, ALSO I.D. AT WEATHERHEAD. 4) NOTE: THE NUMBER 8[?] SERVICE ENTRANCE NUETRAL IS SIZED OK IF THE UNDERGROUNDED SERVICE ENTRANCE CONDUCTOR IS #2 AWG CU. 5) NOTE: INTERIOR CIRCUITS RATED 20 AMPS? 6) USE ALL ΒΌ" HARDWARE FOR RISER SUPPORTS. 7) ACORN CLAMP SUITABLE FOR ONE TERMINATION. 8) EXPOSE 2ND GROUND ROD. 9) NEED WTR AND GAS BOND. |