Permit: T04EL00232

Parcel: 127040530


Addresses:

5050 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00232

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK TO CLEAR
05/06/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) BONDING DEVICES NEED BOTH SIDES OF SERVICE NIPPLE 250.94 2) INSTALL REJECTION PINS 3) SECURE CABLES TO JUNCTION BOX 4) BOND JUNCTION BOX ENCLOSURE 5) USE AN APPROVED FITTING WITH LB ON BOTTOM-CHASE NIPPLE NOT APPROVED