Permit: T04EL00229

Parcel: 113070400


Addresses:

1806 E ADELAIDE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/18/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) SENT TO TEP ON 02/19/04AM
02/13/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ 1) THE GAS PIPING OF EACH UNIT MUST BE INCLUDED IN THE GROUND BOND. JUMPER FROM ONE TO THE OTHER. 2) NEW GROUNDING TO THE WATER PIPES MUST BE INSTALLED. BOTH UNITS ARE TO BE INCLUDED. CORRECT AND RECALL.