Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/11/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/1) SUPPORT GFCI RECEPTACLE BOXES. 2) INSTALL BOND BUSHINGS WHERE USING CONCENTRIC K.O.'S OR REDUCING WASHERS. |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ RE-CALL INSP WHEN TENT WIRED UP. |