Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00209
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :FINAL TO BE ISSUED ONCE CONTROL STATIONS TIED INTO CONTROLLER | |
| 08/03/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LETTER FROM ELECTRICAL CONTRACTOR ON TORQUE OF SWITCH GEAR AS PER MANUFACTURER 2) PLACE ADDRESS LABEL ON OUTISE OF GEAR AND ADD CONTROLLER AND BOASTER 3) LABEL 400 AMP SWITCH IN CONTROLLER (CONTROLLER FOR BOASTER) 4) 3/0 TERMINATIONS LOAD SIDE OF 400 AMP SWITCH ? TERMINATIONS INTO LUGS ALL THE WAY-DO NOT SCORCH STRANDS ON COPPER 5) GROUND BUSHING ON 2" ENTIRES INTO BACK OF GEAR USE ALL STRANDS UNDEGROUND LUG 6) NOTE: #4 SHEET E-2, MISSING #8 GROUND TO GRID AND WATER PIPING 7) SEAL HOLE BOTTOM OF TRANSFORMER 8) PLAN CALLS FOR #2 COPPER TO GROUND RODS |
|
| 08/02/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |