Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/02/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEW JUNCTION BOX INSTALLED TO COMPLY WITH 314.28 A. - YOU STILL HAVE UTILITY CONDUCTORS ALONG WITH PREMISES WIRING IN SAME DEDICATED SERVICE RACEWAY. 344.46 REQUIRES BUSHING. |
| 02/27/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$/ 1) ALL ITEMS TO BE CORRECTED THAT ARE NOT COMPLETED 2) ALUMINUM WIRE KINKED 3) OPEN TAPE, CLEAN AROUND WIRE 4) TOP ENTRY OF SERVICE NOT ALLOWED 5) NEED BUSHINGS INSTALLED 6) CHECK FOR OTHER ITEM SUCH AS CROOKED INSTALLATION |
| 02/24/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 02/18/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$/ A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. - PER CODE LISTING, CANNOT ENTER OR EXIT LOAD CONDUCTORS THRU TOP END WALL. EXPOSE ALUMINUM WIRE AT METER TERMINALS TO CHECK FOR KNICKS. INSTALL BUSHING AT NIPPLE. |
| 02/12/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ MUST TAKE CARE OF ALL OF THE ITEMS NOTED. PANELBOARD TO LAY FLAT AGAINST WALL. PLEASE GO THROUGH LIST AND MAKE ALL CORRECTIONS. |
| 02/04/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO GROUNDING ELECTRODE SYSTEM INSTALLED 2) NO GROUNDING BUSH AT TEP RISER 3) ALUMINUM WIRE KNICKED AT CIRCUMFENCE WHERE THE INSULATION WAS REMOVED 4) TAPING OF SPLIT BOLT CONNECTION WILL NEED RUBBER TAPE AND ELECTRICAL TAPE TO A THICKNESS EQUAL TO EXISTING INSULATION 5) COMBINATION SERVICE ENTRANCE PANEL BOARD INSTALLED CROOKED (WORKMANSHIP) NOT ALLOWING SWING OUT DOOR TO CLOSE OR OPEN PROPERLY 6) PENETRATING TOP END WALL OF SERVICE-NOT ALLOWED PER LISTING AND PER CODE 7) L.R. CONDULET INSTALLED DOES NOT AFFORD PROPER ACCESS WITH COVER FACING WALL (A MAXIMUM 2 1/2") 8) DESCRIBE ? WITH ACCURATELY 9) SUPPORT BOX BELOW SERVICE 10) INSTALL A BUSHING AT ? NIPPLE 11) NO ADDRESS TAG 12) LOOSE FITTINGS 12) IMPROPER CLEARANCE 13) OTHER ITEMS MAY BE REQUIRED |