Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL00208

Parcel: 136125980


Addresses:

9850 E MARY DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/05/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/02/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NEW JUNCTION BOX INSTALLED TO COMPLY WITH 314.28 A. - YOU STILL HAVE UTILITY CONDUCTORS ALONG WITH PREMISES WIRING IN SAME DEDICATED SERVICE RACEWAY. 344.46 REQUIRES BUSHING.
02/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999$/ 1) ALL ITEMS TO BE CORRECTED THAT ARE NOT COMPLETED 2) ALUMINUM WIRE KINKED 3) OPEN TAPE, CLEAN AROUND WIRE 4) TOP ENTRY OF SERVICE NOT ALLOWED 5) NEED BUSHINGS INSTALLED 6) CHECK FOR OTHER ITEM SUCH AS CROOKED INSTALLATION
02/24/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
02/18/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999$/ A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. - PER CODE LISTING, CANNOT ENTER OR EXIT LOAD CONDUCTORS THRU TOP END WALL. EXPOSE ALUMINUM WIRE AT METER TERMINALS TO CHECK FOR KNICKS. INSTALL BUSHING AT NIPPLE.
02/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ MUST TAKE CARE OF ALL OF THE ITEMS NOTED. PANELBOARD TO LAY FLAT AGAINST WALL. PLEASE GO THROUGH LIST AND MAKE ALL CORRECTIONS.
02/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NO GROUNDING ELECTRODE SYSTEM INSTALLED 2) NO GROUNDING BUSH AT TEP RISER 3) ALUMINUM WIRE KNICKED AT CIRCUMFENCE WHERE THE INSULATION WAS REMOVED 4) TAPING OF SPLIT BOLT CONNECTION WILL NEED RUBBER TAPE AND ELECTRICAL TAPE TO A THICKNESS EQUAL TO EXISTING INSULATION 5) COMBINATION SERVICE ENTRANCE PANEL BOARD INSTALLED CROOKED (WORKMANSHIP) NOT ALLOWING SWING OUT DOOR TO CLOSE OR OPEN PROPERLY 6) PENETRATING TOP END WALL OF SERVICE-NOT ALLOWED PER LISTING AND PER CODE 7) L.R. CONDULET INSTALLED DOES NOT AFFORD PROPER ACCESS WITH COVER FACING WALL (A MAXIMUM 2 1/2") 8) DESCRIBE ? WITH ACCURATELY 9) SUPPORT BOX BELOW SERVICE 10) INSTALL A BUSHING AT ? NIPPLE 11) NO ADDRESS TAG 12) LOOSE FITTINGS 12) IMPROPER CLEARANCE 13) OTHER ITEMS MAY BE REQUIRED