Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) THE ADDRESS MUST BE A METAL EMBOSSED OR STAMPED PLATE, PERMANENTLY SCREWED OR RIVITED TO THE PANEL. MAGIC MARKER, PEN, OR PENCIL NOT ALLOWED. SEE ART. 230 NEC. 2) REMOVE THE TY WRAP PLASTIC STRAPS ATTACHING THE GROUND WIRE TO THE RISER PIPE. SUPPORT GROUND WIRES WITH METAL 1 HOLE CLAMPS MADE FOR THE PURPOSE. ATTACH TO WALL. |