Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00175
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ GARAGE NOT TO BE CONNECTED TO ELECTRICAL. RANGE NOT TO BE CONNECTED TO ELECTRICAL. | |
02/11/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) CIRCUIT IN PEDISTAL CONNECTED TO 50 AMP CB RUNS INTO MH - NOT SUPPORTED UNDER FRAME, WHAT IS IT FOR? ALSO OWNER HAS NOT ANSWERED #4 ON LAST WRITE UP FOR PERMITTED STRUCTURE ON SITE [GRAYE] 2) TIM BENEDICT - 247-3443 - OWNER - HAS BEEN NOTIFIED. | |
02/09/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) NO ANSWER AT DOOR. 2) DEAD FRONT COVER MISSING ON PEDESTAL. 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE PEDISTAL. 4) WIRING FOR SHOP FROM PEDISTAL NOT PER CODE. PLEASE VERIFY THAT A PERMIT WAS ISSUED FOR SHOP AND INSP. APPROVED. UNITS MUST BE OPEN FOR INSP. PROOF OF PERMIT AND APPROVED INSP. MUST BE VERIFIED PRIOR TO APPROVAL FOR POWER TURN-ON. 5) FRONT ENTRY LIGHT MISSING. |