Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* SENT TO TEP ON 02/02/04AM |
| 01/29/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ THE OLD GROUNDING SYSTEM IS NO LONGER ACCEPTED ON AN INCREASE, IT IS REQUIRED TO DRIVE TWO GROUND RODS NEAR THE SERVICE AS ALLOWED 6' APART. EVERYTHING ELSE IS OK. CONTRACTOR USED EXISTING GROUND. |