Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* SENT TO TEP ON 03/11/04AM |
| 02/17/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE CONNECTORS SECURE CABLES TO NEW SUB PANEL 373.5 2) ISOLATE GROUND AND NEUTRAL AT SUB PANEL 250.24 3) MAINTAIN WORKING CLEARANCE AT NEW SUB PANEL 110.26 4) FILL UNUSED OPENINGS AT SUB PANEL 5) ADJUST PANEL SO NO MORE THAN 1/4" FROM BOX TO SURFACE 6) LABEL ALL BREAKERS AT SUB PANEL |