Permit: T04EL00168

Parcel: 122080750


Addresses:

2216 N SYCAMORE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 03/11/04AM
02/17/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE CONNECTORS SECURE CABLES TO NEW SUB PANEL 373.5 2) ISOLATE GROUND AND NEUTRAL AT SUB PANEL 250.24 3) MAINTAIN WORKING CLEARANCE AT NEW SUB PANEL 110.26 4) FILL UNUSED OPENINGS AT SUB PANEL 5) ADJUST PANEL SO NO MORE THAN 1/4" FROM BOX TO SURFACE 6) LABEL ALL BREAKERS AT SUB PANEL