Permit: T04EL00164

Parcel: 117030730


Addresses:

811 N 5TH AV


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00164

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/05/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 02/06/04AM
02/02/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ THE CORRECTIONS REQUESTED HAVE NOT BEEN CARRIED OUT.
01/29/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) IDENTIFY THE CIRCUIT FEEDING THE REAR UNIT. IT APPEARS THE UNIT HAS WIRING RATED FOR NOT MORE THAN 20 AMPERES. THE CIRCUIT BREAKER FEEDING THIS UNIT IS NOT IDENTIFIED AT THE MAIN PANEL. 2) THE MAIN SERVICE LOAD PANELS MUST HAVE CIRCUIT DIRECTORIES/INDEXES. 3) THE WIRENUTS ON THE ARIEL CABLE NEED TO BE REPLACED. 4) INSTALL TWO SMOKE DETECTORS IN UNIT.ONE IN BEDROOM AND ONE IN LIVING ROOM.