Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2004 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 02/09/2004 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*/ 1) TRENCH BACKFILLED PRIOR TO APPROVAL OF U.G. INSP. 2) PROVIDE MAIN BREAKER AT SOUTH UNIT, SUB-PANEL. MAIN BREAKER AT BOTH UNITS TO HAVE SUPPLEMENTAL HOLD DOWN DEVICE ON BREAKERS, PER ART 384.16 NEC. 3) LABEL SUB-PANEL 1 & 2. 4) SUB-PANEL AT MAIN HOUSE NOT TO HAVE MAIN BREAKER RATED AT HIGHER AMPERAGE THAN MAIN AHEAD AT SERVICE ENCLOSURE. |
| 01/27/2004 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*/ 1) PERMIT MUST BE FOR BOTH UNITS #1 AND 2 AND ASSOCIATED WIRING TO SUB PANEL UNIT #2 2) U.G. CONDUIT MUST BE 18" MINIMUM BELOW GRADE, MUST USE SCHEDULE 80 WHERE EXPOSED 3) CHASE NIPPLE NOT ALLOWED AT LB UNIT #2 SUB-PANEL, USE CLOSE NIPPLE AND BOND BUSHING ALSO LB COVER MISSING 4) WP, BOX NOT SUPPORTED TO WALL AT UNIT #2 |