Permit: T04EL00134

Parcel: 110111210

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*1) OK TO CLEAR INCREASE 2) ALSO SUBJECT TO TEP APPROVAL
02/10/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 2) MAINTAIN CLEARANCES FOR SERVICE DROP TO POOL WATERS EDGE 680.8 3) AN APPROVED FITTING AT CONDUIT IS NEEDED-CHASE NIPPLE IS NOT APPROVED 4) BOND JUNCTION BOX ENCLOSURE 5) BLUE WIRE NUTS NOT LISTED FOR USE WITH CONDUCTORS LARGER THAN #8