Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 01/20/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) RISER CONDUIT NOT SUPPORTED, 2" CONDUIT NOT SUPPORTED, LB. COVER MISSING 2) GROUNDING SYSTEM NOT INSTALLED, 2 GROUND RODS REQUIRED 6' MINIMUM APART 3) BOND WATER AND GAS PIPING 4) INSTALL PERMANENT ADDRESS LABEL 5) WHITE WIRES CONNECTED TO BREAKERS MUST BE TAPED BLACK 6) PERMIT REQUIRED FOR NEW WIRING INTO HOUSE |