Permit: T04EL00104

Parcel: 137030610


Addresses:

5225 S ANNAPOLIS DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
01/20/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) RISER CONDUIT NOT SUPPORTED, 2" CONDUIT NOT SUPPORTED, LB. COVER MISSING 2) GROUNDING SYSTEM NOT INSTALLED, 2 GROUND RODS REQUIRED 6' MINIMUM APART 3) BOND WATER AND GAS PIPING 4) INSTALL PERMANENT ADDRESS LABEL 5) WHITE WIRES CONNECTED TO BREAKERS MUST BE TAPED BLACK 6) PERMIT REQUIRED FOR NEW WIRING INTO HOUSE