Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00101
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/17/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ USE AN APPROVED METHOD FOR CABLE PROTECTION. | |
| 06/16/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ NO WORK PROGRESS. PAY RE-INSPECTION FEE BEFORE NEXT INSP. | |
| 06/09/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/ NO WORK PROGRESS. |
|
| 06/02/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ PLEASE COMPLETE 2ND ITEM PREVIOUS INSP. | |
| 01/26/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ MAIN BREAKER EXCEEDS 6'-7" IN HIEGHT. UNISTRUT INSTALLED. CANNOT VERIFY RACEWAY FROM BACK OF LOAD CENTER TO WALL. BONDING BUSHINGS AND JUMPER REQUIRED FOR SERVICE RACEWAYS TO ENCLOSURE. |