Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/26/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* / 1) OK TO CLEAR SERVICE UPGRADE 2) SENT TO TEP ON 1/28/04 |
| 01/22/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CLEARANCE OVER ROADWAY TO BE 18' WE HAVE 16'-6" 230.24 2) BONDING JUMBPER TO BE SIZED PER 250.102 AND TABLE 250.66 3) PLEASE BOND JUNCTION BOX |
| 01/21/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) BLUE WIRE NUTS USED TO SPLICE #2 COPPER AT J-BOX TO LEFT OF PANEL ARE ONLY GOOD FOR #6 COPPER - USE CORRECT METHOD. 2) WHERE IS WATER BOND? RE-CALL WHEN CORRECTED. |