Permit: T04EL00091

Parcel: 117042920


Addresses:

329 E 6TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* / 1) OK TO CLEAR SERVICE UPGRADE 2) SENT TO TEP ON 1/28/04
01/22/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CLEARANCE OVER ROADWAY TO BE 18' WE HAVE 16'-6" 230.24 2) BONDING JUMBPER TO BE SIZED PER 250.102 AND TABLE 250.66 3) PLEASE BOND JUNCTION BOX
01/21/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) BLUE WIRE NUTS USED TO SPLICE #2 COPPER AT J-BOX TO LEFT OF PANEL ARE ONLY GOOD FOR #6 COPPER - USE CORRECT METHOD. 2) WHERE IS WATER BOND? RE-CALL WHEN CORRECTED.