Permit: T04EL00075

Parcel: 130100420


Addresses:

3110 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/30/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP ON 02/02/04AM
01/28/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ NO COMPLIANCE WITH NOTES 1 & 5, PREVIOUS INSP.
01/21/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) TWO GROUND RODS REQUIRED FOR GROUNDING SYSTEM, 6' MIN. APART. 2) INSTALL PERMANENT ADDRESS TAG TO ENCLOSURE, MUST BE SCREWED OR RIVITED. 3) BOND WATER AND GAS PIPING. 4) I.D. CIRCUIT BREAKERS. 5) PERMIT REQUIRED FOR NEW DRYER OUTLET. 6) VERIFY C-11 LICENSED CONTRACTOR DOING WORK, NAME AND PHONE #. 7) CABLE TERMINATING AT BOTTOM MUST BE IN CONDUIT.