Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BOND ENCLOSURE PER 250-148. 2) BULB WIRE NUT LISTED FOR NOT LARGER THAN 2 #8 CONDUCTOR, 110-3. 3) BREAKER TO BE LISTED FOR USE BY MANUFACTURER - 110-3 - GE NOT FOR MURRAY. 4) FITTINGS TO BE FOR WEATHERPROOF USE. |
|
| 03/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) INSTALL GROUNDING ELECTRODE SYSTEM AS PER CODE 250-50 AND 250-52. 2) LABEL CIRCUIT BREAKERS. 3) CONNECT BONDING JUMPER. 4) USE CORRECT SIZED CONDUCTORS FOR AMPACITY AND DERATED PER 310-15 AND 310-16. 5) OLD DISCONNECT WILL NOT BE ALLOWED FOR JUNCTION BOX OR PASS THROUGH. 6) PLEASE VERIFY WATER BOND.. |