Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) AN APPROVED FITTINGS ARE NEEDED AT JUNCTION BOX AND LB CHASE NIPPLE NOT APPROVED 2) FILL UNUSE PORTION OF OPENING FOR GROUNDING ELECTRODE CONDUCTOR OR USE ANOTHER OPENING 3) PLEASE LABEL BREAKERS 4) TIGHTEN LUG TO NEUTRAL FOR GROUNDING ELECTRODE CONDUCTOR |