Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 01/16/2004 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 01/12/2004 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245*/ 1) CHANGE PERMIT DESCRIPTION TO SERVICE UPGRADE, THIS IS A NEW SERVICE NOT UPGRADE. 2) BOND GAS AND WTR PIPING. 3) PERM ADDRESS LABEL REQUIRED ON SERVICE ENCLOSURE, MUST BE METAL TAG, SCREWED OR RIVITED. 4) PVC CONDUIT MUST BE SLE. 80 AND GLUED PROPERLY AT ALL JOINTS, SUPPORT TO STRUCTURE. 5) RISER CONDUIT MUST HAVE 2 HOT CONDUCTORS AND 1-NEUTRAL. 6) GROUND WIRE FOR 100A SUB-PANEL TOO SMALL, SHOULD BE A #6 COPPER. |