Permit: T04EL00048

Parcel: 120061360


Addresses:

420 E LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
01/16/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
01/12/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection 0245*/ 1) CHANGE PERMIT DESCRIPTION TO SERVICE UPGRADE, THIS IS A NEW SERVICE NOT UPGRADE. 2) BOND GAS AND WTR PIPING. 3) PERM ADDRESS LABEL REQUIRED ON SERVICE ENCLOSURE, MUST BE METAL TAG, SCREWED OR RIVITED. 4) PVC CONDUIT MUST BE SLE. 80 AND GLUED PROPERLY AT ALL JOINTS, SUPPORT TO STRUCTURE. 5) RISER CONDUIT MUST HAVE 2 HOT CONDUCTORS AND 1-NEUTRAL. 6) GROUND WIRE FOR 100A SUB-PANEL TOO SMALL, SHOULD BE A #6 COPPER.