Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/16/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 01/14/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*SENT TO TEP ON 01/15/04AM |
| 01/09/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) USE PROPER FITTINGS AT CONDUIT TERM - AT BOTTOM AND TOP, SEE LISTING. 2) 2 HOLE STRAPS NOT INSTALLED PROPERLY ON RISER, NEED BACKING BEHIND RISER CONDUIT. 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE, MUST BE SCREWED OR RIVITED. VERIFY LICENSED CONTRACTOR C-11. 4) WIRING ABOVE BUSS LINE BEHIND BARRIER NOT ALLOWED PER LISTING, MUST ENTER AT BOTTOM OR SIDE BELOW BUSS LINE PER SQUARE D LISTING. |