Permit: T04EL00043

Parcel: 129022920


Addresses:

2642 E EXETER ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/16/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
01/14/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 01/15/04AM
01/09/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) USE PROPER FITTINGS AT CONDUIT TERM - AT BOTTOM AND TOP, SEE LISTING. 2) 2 HOLE STRAPS NOT INSTALLED PROPERLY ON RISER, NEED BACKING BEHIND RISER CONDUIT. 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE, MUST BE SCREWED OR RIVITED. VERIFY LICENSED CONTRACTOR C-11. 4) WIRING ABOVE BUSS LINE BEHIND BARRIER NOT ALLOWED PER LISTING, MUST ENTER AT BOTTOM OR SIDE BELOW BUSS LINE PER SQUARE D LISTING.