Permit: T04EL00040

Parcel: 133251030


Addresses:

8550 E COLETTE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/28/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/19/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*/PARTIAL 1)HANDLE TIES ARE NEEDED FOR 2 PAR? BREARERS. 2)FINISH #4 GAS BONDING AND #7 NO ENTRANCE THROUGH METER SECTION AND #10 FOR PARALLEL LOIRE?
03/04/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) STRAP GROUNDING ELECTRODE CONDUCTOR TO BUILDING 3) WHERE IS 2ND GROUND ROD 4) GAS AND WATER BONDS ARE NEEDED 5) PLEASE LABEL BREAKERS 6) RISER STRAP TO BE A2 HOLE AND 1/4" MINIMUM HARDWARE 7) NO ENTRANCE ALLOWED THRU METER SECTION 8) SUPPORT CONDUITS AS PER CODE AND TIGHTEN LOOSE FITTINGS 9) ALL GROUNDING EQUIPMENT CONDUCTOR TO TERMINATE AS PER MANUFACTURERS INSTRUCTIONS 10) BREAKER TO BE SIZED PER CONDUCTOR AMPACITY 11) CONDUIT TO BE BURIED AT 18" DEPTH 12) SUPPORT M/C CABLE AS CODE AND USE APPROVED FITTINGS 13) USE BREAKERS LISTED BY MANUFACTURER 14) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR