Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/16/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* SENT TO TEP 1/20/04 |
| 01/14/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLEASE CLEAN SURFACE UNDER NEW GROUND BAR 2) WHERE DOES WATER AND GAS BOND CONNECT BACK TO SERVICE 3) TIGHTEN LOOSE FITTING 250.104 |
| 01/09/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) BOND JUNCTION BOX - SIZE PER 250-122 |