Case: T04DV00995

Parcel: 111070160


Addresses:

3434 E WATER ST #21


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T04DV00995

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
10/30/2007 INSP - FOLLOW UP CODE ENFORCE Approved COMPLIANT CLOSE CASE
01/18/2006 INSP - FOLLOW UP CODE ENFORCE Correction Required 1/18/06 VISITED SITE, WENT THROUGH PARK'S MAIN ELECTRICAL SYSTEM, B & A ELECTRICAL HAS GONE THROUGH THE SYSTEM, HAS MADE ALL REPAIRS, CALLED AND TALKED WITH JIM FROM B & A ELECTRIC WHO STATED THAT WAS DONE UNDER PERMIT AND ALL WORK WAS APPROVED BY RAY MAHUTA (ELECTRICAL INSPECTOR) ASKED IF B & A COULD SEND OVER A FAX SHOWING PAPER WORK APPROVAL FROM RAY MAHUTA, THIS WAS AGREED WILL FAX OVER PAPER WORK. WHILE ON SITE, LOOKED INTO GARAGE, STORAGE ROOM, MAINT. ROOM, FOUND WORK HAS NOT BEEN DONE IN THIS ROOM, AGAIN CALLED AND TALKED WITH JIM ABOUT THIS ROOM AND HE STATED HE HAS NOT DONE ANY WORK IN THIS ROOM, AGREED TO DO WORK AND SHOULD BE DONE BY MIDDLE OF NEXT WEEK, 1/25-1/26, AGREED TO FINISH F/U INSP. AT THIS TIME.
07/25/2005 INSP - FOLLOW UP CODE ENFORCE Correction Required 7/21/05, CALLED REGIONAL MANAGER HANK DABLE TO LET HIM KNOW I WILL BE VISITING SITE TO FINISH EXTEROR INSP.
UNIT 1
SOUTH SIDE HAD ADDED SUB-PANEL CONNECTED TO OUTSIDE OF MOBILE HOME, ADDED ELECTRIC CIRCUIT TO SOUTHWEST CORNER OF MOBILE HOME.
BACK DOOR LACKS STAIRS.
LACKS PROPER ADDRESSING.
UNIT 2-
LACKS PROPER ADDRESSING
LACKS GAS SHUT OFF VALVE ON SUPPLY SIDE TO MOBILE HOME
USING EXTENSION CORD FROM INSIDE TO EXTERIOR WASHER, DRAIN LINE CONNECTED TO CLEAN OUT.
NEW HOT WATER HEATER (PERMIT?)
UNIT 3-
LACKS PROPER ADDRESSING
HOT WATER HEATER FLUE PIPE NOT PROPERLY INSTALLED.
NEW HOT WATER HEATER (PERMIT?)
TELEPHONE POLE LISTING TO SOUTH SIDE.
COULD NOT FIND SEWER CLEAN OUT.
UNIT 4-
STRUCTURE VACANT-UNSECURED
HOT WATER LACKS P.R.V. DRAIN LINE, COLD WATER SHUT OFF.
UNIT 5-
VACANT-SECURED AT THIS TIME
LACKS PROPER ADDRESSING
ALTERED SEWER LINES AND VENTS.
UNIT 6-
HOT WATER TANK LACKS COLD WATER SHUT OFF
FLUE PIPE NOT PROPERLY INSTALLED
SHEET METAL ABOVE COOLER NEEDS TO BE SEALED.
UNIT 7-
LACKS GAS VAVLE ON SUPPLY SIDE TO MOBILE HOME
LIGHT FIXTURE FRONT NOT COMPLETE
HOT WATER TANK LACKS DRAIN LINE, GAS VALVE NOT EASILY ACCESSABLE, FLUE PIPE TO SHORT, LACKS ENCLOSER.
HAS EXPOSED ROMEX AT PEDESTAL
OVER ACCUMULATION OF TRASH AND DEBRIS
ADDITION ADDED
USING EXTENSION CORD TO SUPPLY SERVICE TO WASHER/DRYER
WASHER DRAIN LACKS P-TRAP
EXPOSED WIRTING TO COOLER
UNIT 8
LACKS GAS VALVE ON SUPPLY SIDE TO MOBILE HOME
MAIN ELECTRICAL SERVICE HAS BEEN ALTERED
UNIT 9-
COOLER DETERIORATED TO A POINT OF UNUSABLE, NOT PROPERLY MOUNTED,
EXPOSED DETERIORATING ROMEX TO PANEL
LIFELINE PLUG INCORRECT TYPE EXPOSING WIRES
EXPOSED ROMEX UNDER MOBILE HOME
WATER LINE TO COOLER LEAKING
HOT WATER TANK LACKS COLD WATER SHUT OFF, LACKS P.R.V. DRAIN LINE, LACKS TOP TO ENCLOSER, FLUE PIPE NOT PROPERLY INSTALLED
GAS METER UNPROTECTED
UNIT 10
HOT WATER TANK LACKS P.R.V. DRAIN LINE
LACKS COLD WATER SHUT OFF
UNIT 11
ADDED ELECTRICAL CIRCUIT TO A/C
ADDED ELECTRICAL CIRCUIT TO REAR OF TRAILER/EXPOSED ROMEX
COOLER LINE LEAKING
UNIT 12
SEWER LINE LACKS CLEAN OUT
H.W.TANK LACKS COLD WATER SHUT OFF
LACKS P.R.V. DRAIN LINE
LIFELINE TO SMALL
UNIT 13-
OK
UNIT 14
ADDED PORCH NOT PROPERLY INSTALLED
CAN NOT GET INTO YARD GATES LOCKED.
UNIT 15
PEDESTAL MISSING DEAD PLATE
ADDED ELECTRICAL CIRCUIT TO REAR
GAS METER ALMOST SITTING ON GROUND, LACKS PROTECTION.UNIT 16
GAS METER LACKS PROTECTION
SHED SITS IN MIDDLE OF 2 TRAILERS
PEDESTAL MISSING DEAD FRONT
NO EXTERIOR W.H.
UNIT 17
CLEAN OUTS NOT PROPERLY INSTALLED.
UNIT 18
GAS LINE NOT PROPERLY SECURED
EXPOSED ROMEX IN SHED
ADDED WATER LINES TO WASHER, DRAIN LINE
ADDITION ADDED TO S/W CORNER NOT INSTALLED TO CODE
UNIT 21
VACANT AND UNSECURED AT THIS TIME.
H.W. TANK LACKS COLD WATER SHUT OFF
LACKS DRAIN LINE
WATER LINES HAS BEEN ALTERED
EXPOSED ABS SEWER LINE
UNIT 22
LACKS GAS SHUT OFF ON SUPPLY SIDE TO MOBILE HOME
H.W. TANK LACKS COLD WATER SHUT OFF
H.W. TANK HAS BEEN REPLACED, NO PERMIT.
50 AMP BREAKER 40 AMP LIFELINE CORD
UNIT 23
COOLER HAS EXTENSION CORD FOR ELECTRIC SERVICE
LACKS PROPER ADDRESSING
CHECK PERMIT FOR NEW PEDESTAL
UNIT 25
PEDESTAL SUPPORT POST DETERIORATED LEANING
PEDESTAL MISSING DEAD FRONT
UNIT 26
EXPOSED ABS SEWER LINE
LACKS CLEAN OUT
EXTENSION CORD FROM FRONT WINDOW TO SHED
UNIT 27
LACKS PROPER ADDRESSING
UNIT 289
LACKS PROPER ADDRESSING
ADDED ELECTRICAL CIRCUIT FOR WAHER/DRYER
COVER PANEL FOR ELECTRICAL SERVICE FALLS OFF
UNIT 30
HOT WATER TANK COLD WATER SHUT OFF NOT ACCESSABLE
UNIT 31
ADDITION ADDED TO EAST SIDE
CAN NOT ENTER YARD LOCKED
ELECT. HAS ADDED ROMEX LINE
SEWER LINE NOT PROPERLY SEALED
UNIT 32
LACKS PROPER ADDRESSING
ELECTRIC SERVICE LOOSE NOT PROPERLY SECURED.
COULD NOT ACCESS SEWER LINE
UNIT 33
LACKS PROPER ADDRESSING
ROMEX ADDED TO SERVICE PANEL
SEWER LINE NOT PROPERLY SEALED
HOT WATER TANK LACKS GAS VALVE
WATER SUPPLY LACKS BACK FLOW PREVENTER
UNIT 34
LACKS BACK FLOW PREVENTER
P.V.C. LINES ADDED
LIFE LINE CORD DOES NOT MATCH BREAKER
UNIT 35
OK
UNIT 36
ENTERY DOOR HAS BEEN REPLACED, TO SMALL
WATER LACKS BACK FLOW PREVENTER, WATER LINES ALTERED TO P.V.C.
A/C NOT PROPERLY SUPPORTED
TRASH AND DEBRIS SCATTERED ABOUT YARDS
CAN NOT ACCESS ELECTRICAL PEDESTRAL
LAUNDRY/STORAGE UNIT
CONVERTED INTO 2 SEPERATE UNITS A/B
UNIT A NEW HOT WATER TANK INSTALLED 50 GAL.
HAS HAD ELECTRIC WORK DONE
WATER LINES ADDED GAS TO WATER HEATER. (CHECK PERMITS)
UNIT 38-
SEVERAL ADDITIONS ADDED
ELECTRICAL CIRCUITS ADDED, SUB-PANEL ADDED TO EXTERIOR OF STRUCTURE.
UNIT 37
VACANT AND SECURED AT THIS TIME
UNIT 39
GAS METER LACKS PROTECTION
ELECTRIC LACKS MAIN DISCONNECT
WATER LINE HAS BEEN REPLACED TO P.V.C.
CAN NOT FIND SEWER LINE, CLEAN OUT OR CONNECTIONS.
UNIT 40 LIFE LINE CORD TO SMALL, AMPS.
WATER LINES REPLACED TO P.V.C., LACKS BACK FLOW PREVENTER
UNIT 41
WATER LACKS BACK FLOW PREVENTER
ELECTRIC BEING SUPPLIED BY ROMEX WITH PLUG
HOT WATER TANK LACKS P.R.VALVE DRAIN LINE
FLUE PIPE NOT PROPERLY SECURED
WATER LINE TO MOBILE 3/8 "
UNIT 42
VACANT AND SECURED AT THIS TIME
UNIT 43
VACANT AND SECURED AT THIS TIME
UNIT 44
GAS LACKS SHUT OFF VALVE ON SUPPLY SIDE TO MOBILE HOME
ADDED A/C UNIT
UNIT 45
LACKS PROPER ADDRESSING
NEW HOT WATER TANK ( CHECK PERMIT)
ELECTRIC HARDWIRED IN WRONG SUB-PANEL
UNIT 46 ELECTRIC SERVICE LABELED WRONG
A/C UNIT ADDED
WATER OR SEWER LEAK UNDER MOBILE HOME
GAS LACKS SHUT OFF ON SUPPLY SIDE TO MOBILE HOME
UNIT 47
LACKS PROPER ADDRESSING
UNIT 48
GAS LACKS SHUT OFF ON SUPPLY SIDE TO MOBILE HOME
ADDITION ADDED, WASHER/DRYER,. PLUMBING ELECTRIC ADDED.
UNIT 49 GAS LACKS SHUT OFF ON SUPPLY SIDE TO MOBILE HOME
ADDED WATER LINE FOR WASHER
STORING HAZARDOUS WASTE IN REAR OF YARD (OIL)
HOT WATER TANK LACKS COLD WATER SHUT OFF, P.R.V. DRAIN LINE, GAS VALVE NOT ACCESSABLE
CAN NOT ACCESS ELECTRIC.
UNIT 50
TRASH AND DEBRIS SCATTERED ABOUT YARDS
LACKS GAS VALVE SUPPLY SIDE TO MOBILE HOME
MAIN WATER SUPPLY LACKS EMERGENCY SHUT OFF HANDLE
LIFE LINE NOT INSTALLED PROPERLY, EXPOSED ROMEX, SPLICED CONNECTIONS,
CAN NOT ACCESS SEWER
UNIT 51
GAS METER BENT OVER LIKE BEING HIT BY VEHICLE, LACKS PROPER PROTECTION
LACKS SHUT OFF VALVE ON SUPPLY SIDE TO MOBILE HOME
COOLER LEAKS
ELECTRIC METER LOOSE
WIRING DETERIORATED BAD, EXPOSED ELECTRIC
OPEN AND EXPOSED SEWER LINE MISSING CAP HAS OVER FLOWED PREVIOUSLY.
06/02/2005 INSP - FOLLOW UP CODE ENFORCE Correction Required 6/1/05, VISITED SITE, INSP. ORTA ASST., WENT TO MANAGEMENT OFFICE, TALKED WLITH MARIA WHO IN TURN CALLED CARLOS, MANAGER, CARLOS STATED HE DOES NOT KNOW IF WORK HAS BEEN DONE OR NOT, IN TURN GAVE ME THE NUMBER TO HANK BABLE WHO IS REGIONAL MANAGER, CALLED HANK WHO AGREED TO MEET ON SITE, WHILE WAITING MYSELF AND INSP. ORTA STARTED WALKING PROPERTY TO SEE IF ANY WORK TO ELECTRICAL SYSTEM HAS OCCURED. STARTED AT MAIN ELECTRICAL SERVICE, FOUND NOTHING HAS BEEN DONE, AT THIS TIME HANK SHOWED UP ON SITE, WENT OVER SOME ISSUES AND HANK EXPLAINED THAT NEW OWNERS BETHANY GARDENS 35 LP HAS NO RECORED OF THIS, SHOWED WHERE CERTIFIED MAIL CARD HAD BEEN SIGNED, CARD WAS SIGNED BY OLD OWNER, WITH THIS IN HAND TALKED WITH HANK ABOUT ISSUES SHOWED HANK N/O, EXPLAINED TO HANK THAT I WOULD REVISE THIS N/O MAKE ONE FOR NEW OWNERS, HANK AGREED TO STOP AT OUR OFFICE TO PICK UP COPY, ALSO WILL SEND ONE CERTIFIED TO NEW OWNERS. CONTACT NUMBER IN PEOPLE.